Model: | Outdoor | Rated Voltage: | 7.2kV, 12kV, 17.5kV, 24kV, 36kV, 40.5kV |
---|---|---|---|
Rated Current: | 400A 630A, 1250A, 1600A, 2000A, 2500A, 3150A, | Frequency: | 50/60Hz |
Medium: | SF6 | Material: | Galvanized Sheet And Accessories |
Standard: | GB, IEC Standard | Function: | Control And Protection |
Highlight: | LW8-40.5KV SF6 Gas Circuit Breaker,33kv SF6 Gas Circuit Breaker,35KV SF6 Gas Circuit Breaker |
1. LW8-40.5KV 35KV 33kv outdoor sf6 gas circuit breaker vcb
LW8A-40.5 circuit breaker which is outdoor type finds its universal range of applications for the electrical system with elevation not greater than 2000m,ambient temperature not lower than -30℃,dirtiness grade not high than IV, alternating current 50Hz and the maximum voltage 126kV. It is used for cutting the rated current, malfunction current or switching the circuitry, to control and protect the electrical system ,and it can also be used for connecting with the circuit breaker.
2. Parameter List
No. | Item | Unit | Data | |
1 | Rated voltage | KV | 40.5 | |
2 | Rated current | A | 2000 | |
3 | Rated frequency | HZ | 50 | |
5 | Rated short circuit breaking current | KA | 31.5 | |
6 | Rated short-circuit current (peak) | KA | 50 | |
7 | Rated short-circuit withstand current | KA | 20 | |
8 | Rated short circuit closing current(peak) | KA | 50 | |
9 | Electrical life of rated short circuit breaking current | times | 30 | |
10 | Rated short circuit duration | s | 4 | |
11 | Rated line charging close current | A | 31.5 | |
12 | Rated operation sequence | O-0.3s-CO-180s-CO | ||
13 | Split time | ms | ≤60 | |
14 | Closing time | ms | ≤100 | |
15 | Velocity of rigid composite | m/s | 3.2 | |
16 | Velocity of rigidity | m/s | 3.4 | |
17 | Mechanical life | times | 6000 | |
18 | Quality of each circuit breaker | kg | 1400 |
3. Product Standard and application
LW8A-40.5 type outdoor SF6 circuit breaker is an outdoor device used in AC 50HZ three-phase 40.5KV power system. It is applicable to locations that need frequent operating in rated current or under repeatedly on/off short circuit current. Containing the current transformer for measurement and protection, it can directly replace SW2-35 less oil circuit breaker and various types of oil circuit breaker with transition bracket. It can also be used as a tie breaker and switching capacitor group situations with CT14 type spring mechanism.
Products Standards is as below:
GB1984
GB/T28001-2011 idt OHSAS18001:2007
GB/T24001-2004 idt ISO14001:2004
4. Photo and drawing
5. Factory
6. Delivery
7. FAQ
1. Send the technical data, better for all useful information; we will make a good recommendation.
If possible please attach one reference picture to avoid any misunderstanding or any links from our website for we get a better understanding.
2. The lead time depend on quantity of order. Some standard type is on stock. Otherwise, it will take 3-15 days.
3. Usually shipped by sea, small order or urgent order we can send you by air.
4. All our activities are accredited to ISO 14001:2015 and IEC standard.
5. Technology ensure the quality satisfy international request.